Xinysun Instrument (Shanghai) Co., Ltd.

Products

PRODUCTS

Breadcrumb: Home > Products > Industrial Test Instruments > Tachometers

LUYOR-910 Series Panel-Mount Tachometer
  • LUYOR-910 Series Panel-Mount Tachometer

  • LUYOR-910 Series Panel-Mount Tachometer

  • LUYOR-910 Series Panel-Mount Tachometer

LUYOR-910 Series Panel-Mount Tachometer

Overview

LUYOR-910 panel mount tachometer, 5-999990 RPM, +/-0.001% of reading, 2 relay alarms, 0-5V or 4-20mA output, RS485 option, 96x48mm bezel.

Model:UYOR-910
Updated:2026-11-14
Manufacturer:LUYOR
Reference price:¥3,400
Datasheet:Download datasheet
Views:
DetailsSend inquiry
5-999990 RPMwide range, low speed to high speed equipment
±0.001%of reading, NIST compliant
2 relayshigh/low alarms, latch and hysteresis settable
0-5V / 4-20mAanalog output, optional RS485
96×48mmstandard panel meter, 92×44mm cutout
5V / 24Vsensor power from the meter

What Problem This Meter Solves

A machine shaft has to be monitored continuously, but the people in the control room cannot see the machine. A hand-held tachometer can take a reading, but it cannot watch all the time or trigger an alarm. Separating measurement from viewing calls for a split speed measurement system: a sensor reads speed without contact, and a meter displays it, raises alarms and sends the signal out.

LUYOR-910 is the meter half of that system: panel-mount, standard 96×48mm bezel (92×44mm cutout), flush with the cabinet door or console face once installed. The measuring end comes from the LUYOR speed sensor range - the ROLS-5PW laser model, the ROS photoelectric series and the ROS-HT-W-25 high-temperature model all connect directly; third-party sensors or devices that output 0-5V TTL pulses (proximity switches, encoders and so on) also work, and 1.5-50V AC signals are within the input range.

Beyond the reading, its more important role is automatic judgment: each of the two alarm setpoints drives its own relay, so an out-of-limit speed triggers an action that can stop the machine, light a warning or notify the control room. Analog and RS485 outputs feed speed data into a PLC, recorder or host system, closing the monitoring loop.

Measurement and viewing separated, flush panel mounting  the sensor measures without contact at the machine, the 910 displays it in the control cabinet panel; standard 96×48mm bezel, 92×44mm cutout, only 90mm deep, so it takes little space inside the door.
From display to reporting in one unit  dual relay alarms drive on-site action, 0-5V / 4-20mA feed recorders and PLCs, RS485 (Modbus RTU) connects to SCADA; one meter does all three jobs.

Installation and Wiring in Four Steps

Step 1: Cut the Panel and Insert the Meter

Cut a 92×44mm opening in the cabinet door or console panel, push the body in from the front and tighten the supplied bracket from behind. Overall depth is 90mm, so shallow cabinets work too. For bench use or temporary setups, the optional LUYOR-910BOX housing needs no cutout and sits on a desk with a full terminal panel.

Step 2: Connect the Three Sensor Wires

Take the ROLS-5PW laser sensor: brown (power +) goes to terminal 7 (5V), blue (GND) to terminal 5 (COM), black (signal) to terminal 1 (IN). Other LUYOR sensors follow the same color code. The meter can supply 5V or 24V to the sensor, so no separate power supply is needed.

Step 3: Connect Working Power

XA AC series: terminals 11 and 12 take 110V or 220V AC. XD DC series: terminal 11 to 24V positive, terminal 12 to 24V negative. Both versions have identical functions; choose at order time to match the cabinet.

Step 4: Connect the Outputs

Analog output is on terminals 19 and 20 (19 negative, 20 positive) for a recorder or PLC analog input. RS485 is on terminals 9 and 10 (9 = A, 10 = B) for SCADA or data acquisition. The two relay outputs drive alarms, indicator lamps or interlock circuits directly.

Scale factor and alarm values are set on site:the scale factor (1-999999), alarm values, latch mode, hysteresis and low-limit lock are all set with the panel keys and survive power loss. Changing the sensor or the monitored machine just means resetting them; no return to factory and no PC needed.

Core Specifications

999990RPM range top
measurement starts at 5 RPM
±0.001%of reading
NIST standard
6 digits14mm high LED
dual-row display
2 Hzdisplay refresh
above 120RPM
ItemSpecification
BrandLUYOR
Product typePanel-mount tachometer (display and alarm end of a split speed measurement system)
Range5-999990 RPM
Accuracy±0.001% of reading or ±1 in the last digit (standard update); ±0.006% of reading or ±1 in the last digit (fast update); NIST compliant
Resolution0.001-10 RPM (in the 100000-999990 RPM range)
Display6-digit 14mm high LED, dual row PV measured value / SV setpoint, refreshed twice per second
Input configurationLUYOR speed sensors / 0-5V TTL pulse / 1.5-50Vac signal
Alarm2 alarm setpoints, high or low, latching or non-latching, hysteresis and editable low-limit lock
Alarm outputTwo Form C relays, contact rating 1A @ 230Vac
Analog output0-5Vdc voltage or 4-20mA current (by model)
CommunicationOptional RS485, Modbus RTU protocol
Scale / totalizerScale factor 1-999999; totalizer/counter display 0.001-999999
Sensor supply5Vdc or 24Vdc (output from the meter)
PowerXA: 100-240Vac 50/60Hz; XD: 24Vdc (by model)
DimensionsBezel 96×48mm, cutout 92×44mm, depth 90mm
OptionsLUYOR-910BOX panel meter housing (desktop use, no cutout)
NIST compliant:the LUYOR-910 is calibrated to NIST standards at the factory, and ±0.001% of reading is metrology-grade for a speed meter, so it can serve as a reference for production line speed monitoring and acceptance testing.

Choosing an Ordering Code

The code has three parts: power (XA AC / XD 24V DC) + analog output (DC 0-5V voltage / MA 4-20mA current) + whether RS485 is fitted. Start with what the cabinet supplies, then with what the downstream device accepts:

Ordering codePowerAnalog outputRS485Typical destination
LUYOR-910XA-DC100-240V AC0-5V voltage-Recorders, voltage input cards
LUYOR-910XA-MA100-240V AC4-20mA current-PLC analog inputs, secondary meters
LUYOR-910XA-DC-RS485100-240V AC0-5V voltageYesVoltage acquisition plus SCADA/data acquisition
LUYOR-910XA-MA-RS485100-240V AC4-20mA currentYesPLC plus SCADA/data acquisition
LUYOR-910XD-DC24V DC0-5V voltage-DC control cabinets, mobile equipment
LUYOR-910XD-MA24V DC4-20mA current-DC cabinets with PLC analog input
LUYOR-910XD-DC-RS48524V DC0-5V voltageYesDC cabinets plus SCADA/data acquisition
LUYOR-910XD-MA-RS48524V DC4-20mA currentYesDC cabinets plus PLC and SCADA
Selection rule:power follows the cabinet (XA for AC cabinets, XD for DC), signal follows the downstream device (DC for voltage inputs, MA for current loops), and add RS485 when data goes to SCADA or a data acquisition system. Relay alarms, 5V/24V sensor supply and the display are identical on every model.

LUYOR-910 or LUYOR-912

The two meters are two forms of the same split-measurement approach and share the same sensor range; the difference is mounting position and output emphasis: the 910 is panel-mount and focuses on local display and alarms, the 912 is 35mm DIN rail and focuses on signal transmission and remote monitoring. If unsure, use the table below:

ItemLUYOR-910 panel tachometerLUYOR-912 intelligent speed transmitter
MountingPanel cutout, flush (92×44mm cutout)35mm standard DIN rail clip-on
RoleLocal display + alarm + transmissionSignal transmission + remote monitoring + alarm
Display6-digit LED, PV/SV dual row, 14mm high6-digit LED, PV red 9mm / SV green 6.5mm
Accuracy±0.001% of reading (NIST standard)Transmission accuracy 0.2% FS
Relays2 Form C, 1A @ 230Vac2 Form C, AC220V/3A, 100000 operations
CommunicationOptional RS485 (Modbus RTU)Standard RS485, opto-isolated (Modbus RTU)
Power100-240Vac or 24VdcAC85-260V, 4W
Typical useOperator positions that read and alarm at the cabinet doorAutomation and data acquisition into PLC/DCS/SCADA

Many projects use both: a 912 on the rail beside the machine sends the signal to the control room, and a 910 in the cabinet door gives the operator a local reading and alarm; with the same sensor model and scale factor, the two readings check each other. Full 912 specifications are on the LUYOR-912 intelligent speed transmitter / speed monitor product page.

Typical Applications

Production Line Motors and Fans

For motors, fans and pumps that run continuously, aim the sensor at a reflective mark or keyway and the 910 shows speed continuously on the cabinet panel; when speed falls below the process minimum the relay acts, flagging a stall or an idle run.

Overspeed Protection and Interlocked Shutdown

Set the alarm to the process maximum and wire the relay output into the stop circuit: centrifuges, sand mills and test rigs with overspeed risk get a protection layer that is independent of the PLC.

Test Rigs and Acceptance Measurement

±0.001% of reading with NIST calibration backing suits rig testing and acceptance reference speeds for motors and gearboxes; the analog output feeds a recorder for a curve at the same time.

PLC and SCADA Data Acquisition

4-20mA or RS485 carries speed into the PLC and host system for monitoring and storage alongside temperature and pressure; RS485 models use Modbus RTU, configured once.

University Laboratory Teaching

The 24V DC XD series suits mobile lab rigs; with the 910BOX housing no cutout is needed, so one meter demonstrates the measurement principle, alarm logic and signal transmission.

Retrofit of Older Equipment

For machines with no speed monitoring, add a sensor at the shaft and cut one hole in the door; existing pulse sources such as proximity switches and encoders connect directly, without touching the original control system.

Choosing the Matching Sensor

The 910 is only half the system; the measuring end is chosen from the LUYOR sensor range by distance and environment.

Frequently Asked Questions

Is the LUYOR-910 a tachometer or a sensor?

It is the tachometer (display and control end) and has no measuring function of its own; it pairs with a speed sensor to form a split system. The sensor measures without contact at the machine, and the 910 displays, alarms and outputs signals in the cabinet panel. Sensors and meters can be bought separately or as a set.

Which sensors and signal sources can it accept?

Three-wire LUYOR photoelectric and laser sensors connect directly. Third-party sensors that output 0-5V TTL pulses (proximity switches, Hall sensors, encoders and so on) also work, and 1.5-50Vac AC signals are within the input range. State the signal source type at order time so compatibility can be confirmed.

0-5V or 4-20mA output: which one?

Look at the downstream device: choose DC (0-5V) for voltage inputs on recorders and data acquisition cards; choose MA (4-20mA current loop) for PLC analog inputs and for long runs or high-noise environments. If both are needed, take an RS485 model and run analog and digital in parallel.

What can the RS485 version do?

It uses Modbus RTU to send real-time speed as a digital value to SCADA software, a data acquisition system or the 485 port of a PLC; several meters can share one bus and be polled in turn. Unlike analog, it does not drift and needs no calibration, which makes it the recommended choice for data acquisition projects.

How are the two relay alarms configured?

The two setpoints are independent; each can be high or low, latching or non-latching, with hysteresis and an editable low-limit lock. They are changed with the panel keys and survive power loss. A common setup is one setpoint at the upper limit for overspeed protection and one at the lower limit for stall warning.

What is the panel cutout, and where does it mount?

Bezel 96×48mm, cutout 92×44mm, overall depth 90mm. It fits cabinet doors, console panels and distribution box panels; the body pushes in from the front and the rear bracket locks it. For temporary use without a cutout, choose the LUYOR-910BOX housing.

What power options are there?

XA series: 100-240V AC 50/60Hz, straight onto 220V mains. XD series: 24V DC, for DC cabinets, mobile rigs or laboratories. Functions are identical; just specify at order time.

Does the sensor need its own power supply?

No. The meter outputs 5V or 24V to power the sensor, so three wires are enough. This also avoids signal faults from a mismatched sensor supply, one of the conveniences of using LUYOR meters and sensors as a set.

How is the ROLS-5PW laser sensor wired?

Brown (power +) to terminal 7 (5V), blue (GND) to terminal 5 (COM), black (signal) to terminal 1 (IN). Other models follow the same color code; the Installation and Wiring in Four Steps section above has the full description.

How accurate is it really? Can it serve as a reference meter?

±0.001% of reading or ±1 in the last digit at the standard update rate, NIST compliant; ±0.006% of reading at the fast update rate. That is accurate enough to serve as a reference for production line speed acceptance and for checking other tachometers.

How does it relate to the LUYOR-912?

Two forms of the same measurement system: the 910 is panel-mount and focuses on local display and alarms; the 912 is rail-mount and focuses on transmitting signals into PLCs and SCADA. They share the same sensors; see the comparison table above. For automation projects, look at the 912 first.

Can a hand-held tachometer replace it?

A hand-held unit such as the PLT200 suits spot checks on patrol, but it cannot monitor continuously, alarm automatically, or provide analog and communication outputs. For 24/7 monitoring or integration with a control system, the split 910 system is the right tool.

What is the LUYOR-910BOX housing?

A metal housing matched to the meter body that turns the panel-mount unit into a standalone desktop instrument with a full terminal panel; it suits laboratories, temporary testing and places where a cutout is impractical. Ordered separately from the meter.

What about lead time and warranty?

Common models are in stock or ship short; confirm lead time for specific configurations such as RS485 and for volume orders. Warranty and service follow LUYOR's official terms. Units ship from Shanghai, with selection confirmation, wiring guidance and follow-up support.

How do I request a quote, and what do you need to know?

Three things: the power available (AC or 24V DC), what the meter connects to downstream (which decides analog output and whether RS485 is needed), and which sensor you plan to use (or ask us to recommend). A complete request usually gets a configuration and price the same day.

Documents and Service

Documents Available

  • LUYOR-910 product literature and official specifications

  • Comparison table of the eight ordering codes

  • Panel cutout dimensions and housing notes

  • Wiring diagrams for each sensor (ROLS-5PW / ROS / ROS-HT)

  • Modbus RTU register map

  • Quotation for sensors and complete systems

Service Support

  • Meter and sensor configuration recommended for your site

  • Ordering code confirmation and alternative suggestions

  • Guidance on wiring, scale factor and alarm settings

  • Technical support for Modbus integration with SCADA and PLCs

  • Troubleshooting and tuning of alarm interlock schemes

  • Volume purchasing and project quotations

Send inquiry

Message

  • Product Name:

  • Company:

  • Your Name:

  • Phone:

  • Email:

  • Province / Region:

  • Address:

  • Message:

Copyright 2026 Xinysun Instrument (Shanghai) Co., Ltd. All rights reserved.
ICP:ICP-2026046447

SiteMap

Official WeChat QR code

WeChat QR
Official WeChat QR code Follow

Official WeChat QR code

Contact

131-2093-6518

Top